13kV Rewinds

Large motor repair

High Voltage Motor Rewinding through 13.8kV

Inman Electric Motors rewinds high voltage motors through 13,800 volts. The windings are either processed with vacuum pressure impregnation (VPI), B-stage coils, or both. High voltage motors are wound with coils that fit snugly into the core slots with minimum clearance between the core and the coils to prevent partial discharge. Coils are isolated from one another and well insulated. The connections are meticulously insulated, secured, blocked, tied, and isolated. An outer layer of conductive tape on the straight sections of the coils is essential. All coil measurements and fits are documented. Electrical tests are performed according to IEEE standards and manufacturers specifications.